Solar Power Cable

Extra Flexible Power Supply Systems Cable


WARNING: California Proposition 65 - Cancer and Reproductive Harm
www.P65Warnings.ca.gov


Part
Number
Size Stranding
*
Insulation Nominal OD UL Style
***
AMPS
**
Weight
AWG MM2 IN MM IN MM LBs/MFT KGs/Meter
A2006B 6 13.3 266 X 30 0.060 1.52 0.342 8.69 UL 1232, UL 1283, UL 10269 118 136 0.202
A2004B 4 21.15 420 X 30 0.060 1.52 0.386 9.80 UL 1232, UL 1283, UL 10269 157 189 0.281
A2002B 2 33.61 665 X 30 0.060 1.52 0.446 11.33 UL 1232, UL 1283, UL 10269 213 292 0.435
A2001B 1 42.4 836 X 30 0.080 2.03 0.520 13.21 UL 1232, UL 1284, UL 10269 246 350 0.521
A2110B 1/0 53.5 1064 X 30 0.080 2.03 0.575 14.61 UL 1232, UL 1284, UL 10269 291 450 0.670
A2120B 2/0 67.4 1330 X 30 0.080 2.03 0.610 15.49 UL 1232, UL 1284, UL 10269 336 551 0.820
A2130B 3/0 85.0 1672 X 30 0.080 2.03 0.685 17.40 UL 1232, UL 1284, UL 10269 392 672 1.000
A2140B 4/0 107 2109 X 30 0.080 2.03 0.745 18.92 UL 1232, UL 1284, UL 10269 454 820 1.220
AT250MB 250 MCM 127 2527 X 30 0.100 2.54 0.835 21.21 UL 1284, UL 1339, UL 10269 510 962 1.432
A1350MB 350 MCM 177 3458 X 30 0.100 2.54 0.965 24.51 UL 1284, UL 1339, UL 10269 638 1,280 1.905
A1530MB 500 MCM 253 5054 X 30 0.100 2.54 1.130 28.70 UL 1284, UL 1339, UL 10269 784 1,868 2.780
A1750MB 750 MCM 380 7448 X 30 0.115 2.92 1.380 35.05 UL 1284, UL 10269 951 2,719 4.046
* Extra flexible conductor with soft drawn bare copper to ASTM Specifications B172. Also available in tinned copper.
**The 105°C cable ampacities are adapted from ICEA P-54-440/NEMA WC51-1986(R1991). The ampacities are provided for informational purposes only. Acceptance of these values by any governing authority is the responsibility of the end user. Ampacities are based on a single conductor, in free air, at 30°C ambient air temperature.
*** 1/0 AWG thru 4/0 AWG also UL 1338 & UL 10070.

 

Specification

This product was designed to meet or exceed all test requirements called for by the Underwriters Laboratories and the National Electric Code, and is recommended for use in accordance with UL and CSA for internal wiring of uninterruptible power supply equipment, UL standard 1778. Also suitable for use in transformers, switchboard panels, controls, electronic circuits and meters. It can be used as battery cable, battery charger cable, motor lead, and power hookup cable.

 

Insulation

This product offers a unique flame retardant polyvinyl chloride compound (VW-1), and is moisture, abrasion, acid, diesel fuel and oil resistant. It is extremely flexible and easy to work with.

 

Features

  • 105°C - 600/1000 Volt
  • "CT" Approved 1/0 AWG through 750 MCM
  • FT4 Rated
  • Available in Tinned or Bare Copper Stranding

 

UL ul recognized CSA nec rohs
UL Listed UL Recognized CSA NEC Types Rohs Compliant
MTW or THW
BC-5W2
Style 1232
Style 1283
Style 1284
Style 1339
Style 10070
Style 10269
TEW A/B FT-1 on 6 AWG to 4/0 AWG
AWM A/B FT-1 on 250 MCM to 750 MCM
MTW & THW