Extra Flexible Battery Cable

Marine Wire & Cable that Meets the Standards of UL & ABYC

Part
Number
Size Stranding
*
Insulation Nominal OD UL Style
***
AMPS
**
Weight
AWG MM2
IN
MM
IN
MM
LBs/MFT
KGs/Meter
A2006T 6 13.3 266 X 30 0.060 1.52 0.342 8.69 1232-1283-10269 118 136 0.202
A2004T 4 21.15 420 X 30 0.060 1.52 0.386 9.80 1232-1283-10269 157 189 0.281
A2002T 2 33.61 665 X 30 0.060 1.52 0.446 11.33 1232-1283-10269 213 292 0.435
A2001T 1 42.4 836 X 30 0.080 2.03 0.520 13.21 1232-1284-10269 246 350 0.521
A2110T 1/0 53.5 1064 X 30 0.080 2.03 0.575 14.60 1232-1284-10269 291 450 0.670
A2120T 2/0 67.4 1330 X 30 0.080 2.03 0.610 15.49 1232-1284-10269 336 551 0.820
A2130T 3/0 85.0 1672 X 30 0.080 2.03 0.685 17.40 1232-1284-10269 392 672 1.000
A2140T 4/0 107 2109 X 30 0.080 2.03 0.745 18.92 1232-1284-10269 454 820 1.220
* Extra flexible conductor with soft drawn bare copper to ASTM Specifications B172. Also available in tinned copper.
**The 105°C cable ampacities are adapted from ICEA P-54-440/NEMA WC51-1986(R1991). The ampacities are provided for informational purposes only. Acceptance of these values by any governing authority is the responsibility of the end user. Ampacities are based on a single conductor, in free air, at 30°C ambient air temperature.
*** 1/0 AWG thru 4/0 AWG also UL 1338 & UL 10070.

 

Specifications

This product was designed to meet or exceed all test requirements called for by the Underwriters Laboratories and the National Electric Code, and is recommended for use in accordance with UL and CSA for internal wiring of uninterruptible power supply equipment, UL standard 1778. Also suitable for use in transformers, switchboard panels, controls, electronic circuits and meters. It can be used as battery cable, battery charger cable, motor lead, and power hookup cable.

 

Insulation

This product offers a unique flame retardant polyvinyl chloride compound (VW-1), and is moisture, abrasion, acid, diesel fuel and
oil resistant. It is extremely flexible and easy to work with.

 

Features

  • 105°C - 600/1000 Volt
  • FT4 Rated
  • Tinned Copper Conductor

 

ul listed ul recognized csa nec rohs
UL Listed UL Recognized CSA NEC Types Rohs Compliant
MTW or THW
BC-5W2
Style 1232
Style 1283
Style 1284
Style 1339
Style 10070
Style 10269
TEW A/B FT-1 on 6 AWG to 4/0 AWG AWM A/B FT-1 on 250 MCM to 750 MCM MTW & THW